Carrier® WeatherMaker™ - 5 Ton, 14 SEER, Packaged Rooftop Gas Heat & Electric Cool Unit (208/230-1-60)

Item: 48KCEA06A2A3-0A0A0
MFR: 48KCEA06A2A3-0A0A0

Store Inventory

Sign in to see real-time inventory at the stores closest to you.
Equipment part list is available.
What’s the price?
Sign in for pricing.
Decrease quantity
Increase quantity

Description

48KCEA06A2A3-0A0A0
48 =
Gas Heat Packaged Rooftop
KC = Standard 14 SEER Efficiency
E = Medium Gas Heat
A = Standard One Stage Cooling Models
06 = 5 ton
A = None
2 = Medium Static Option
A = Al/Cu - Al/Cu
3 = 208-230/1/60
0 = Electro-mechanical Controls can be used with W7212 EconoMi$er IV (Non-Fault Detection and Diagnostic
A = None
0 = None
A = None
0 = Standard
*Contact your Carrier Expert for more details.

The Carrier rooftop unit (RTU) was designed by customers for customers. With “no-strip screw” collars, handled access panels, and more we’ve made your unit easy to install, easy to maintain and easy to use.


Easy to install:
All WeatherMaker® units are field-convertible to horizontal air flow which makes it easy to adjust to unexpected job site complications. Lighter units make easy replacement. Carrier 48KC rooftops fit on existing Carrier curbs dating back to 1989. Also, our large control box gives you room to work and room to mount Carrier accessory controls.
Easy to maintain:
Easy access handles by Carrier provide quick and easy access to all normally serviced components. Our “no-strip” screw system has superior holding power and guides screws into position while preventing the screw from stripping the unit’s metal. Take accurate pressure readings by reading condenser pressure with panels on. Simply remove the black, composite plug, route your gauge line(s) through the hole, and connect them to the refrigeration service valve(s).
Easy to use:
The newly designed, central terminal board by Carrier puts all your connections and troubleshooting points in one convenient place, standard. Most low voltage connections are made to the same board and make it easy to find what you’re looking for and easy to access it. Carrier rooftops have high and low pressure switches, a filter drier, and 2-in (51mm) filters standard.

FEATURES AND BENEFITS
  • Single cooling stage models are available from 3 - 5 ton.
  • SEER up to 14.1.
  • EER’s up to 12.0.
  • Up to 28% lighter than similar industry units. Lighter rooftops make easier replacement jobs.
  • Utility connections are the same because 3 - 5 ton units fit on existing Carrier rooftop curbs. This saves time and money on replacement jobs.
  • Standardized components and layout. Standardized components and controls make service and stocking parts easier.
  • Scroll compressors on all units. This makes service, stocking parts, replacement, and troubleshooting easier.
  • Field convertible airflow. Being able to convert a unit from vertical airflow to horizontal makes it easy to overcome job site complications.
  • Standard Direct Drive - ECM indoor motor with optional belt drive system to meet nearly all applications.
  • Provisions for bottom or side condensate drain.
  • Capable of thru-the-base or thru-the-curb gas line routing.
  • Single-point gas / electrical connection.
  • Sloped, composite drain pan sheds water; and won’t rust.
  • Standardized controls & control box layout. Standardized components & controls make stocking parts & service easier.
  • Tool-less filter access door.
  • Clean, large, easy to use control box.
  • Color-coded wiring.
  • Large, laminated wiring and power wiring drawings which are affixed to unit make troubleshooting easy.
  • Single, central terminal board for test and wiring connections.
  • Fast-access, handled, panels for easy access on normally accessed service panels.
  • “No-strip” screw system guides screws into the panel & captures them tightly without stripping the screw, the panel, or the unit.
  • Mechanical cooling (115°F to 40°F or 46°C to 4°C) standard on all models. Winter Start Kit allows cooling operation down to 25°F (-4°C) and MotorMaster to -20°F (-29°C).
  • High efficiency, gas heat with induced-draft flue exhaust design.
  • Induced draft motor ensures no flue gas can escape into the indoor air stream.
  • Carrier designed naturally draining heat exchanger, unlike positive pressure heat exchangers, do not need to be periodically, manually drained. This saves labor and maintenance expense.
  • 2-in (51mm) disposable filters on all units.
  • Refrigerant filter-drier on each circuit.
  • Each circuit is protected with a high and low pressure switch.
  • Many factory-installed options ranging from air management economizers, 2 position dampers, plus convenience outlets, disconnect switches and smoke detectors.
  • Standard (parts only) Warranty: 15 yr. Stainless steel, 10 yr. aluminized heat exchanger, 5 yr. compressor, 1 yr. parts.
  • Factory-installed Humidi-MiZer® adaptive dehumidification system on all sizes with round tube / plate fin condenser coils, includes MotorMaster I controller.

Documentation

Specifications

Weight597 Pound (lb.)
Width74.375 Inches (in)
Height41.375 Inches (in)
Country of OriginMEX
UPC or Barcode1P48KCEA06A2A3-0A0A0
Hazardous MaterialNo
EPA Cert RequiredNo
Length44 Inches (in)
AFUE80%
Air FlowConvertible
Blower Motor RPM1035-1466
BrandCarrier
BTU Input90000
BTU Output73000
CFM Cooling1500-2500
CFM Heating1050-2730
ColorGray
Condenser Motor HP1/4 HP
Cooling Capacity58500
Cycle/Hertz60
Drive TypeBelt
EER12
Energy Star RatedNo
Equipment TypeGas Electric
Heating Capacity73000
ISO CodeMX
Number of Fan Blades1
PhaseSingle
Product Family48KCE
RefrigerantR-410a
SEER14
StageSingle
TierWeatherMaker
Tonnage5
Voltage208-230 VAC